Spent a Fortune on New Fire Doors and Still Not Compliant?

Michal Burski
Technical Guides
Sealant: Use the correct sealant and backing material in accordance with the manufacturer’s tested installation details, including the permitted gap widths and sealant depths. Where the frame-to-wall gap exceeds these limits, follow the manufacturer’s guidance on a suitable subframe or lining to reduce the structural opening, or contact the manufacturer for further advice before proceeding.

Why a certified fire door product does not guarantee a compliant installation, and what evidence you should expect

This article provides general information on good practice for verifying fire door installations. It is not legal advice. Building owners and managers should confirm specific compliance requirements with a qualified fire risk assessor or competent fire door specialist.

You've Paid for New Fire Doors. Does That Mean You're Compliant?

You've invested in new fire doors, appointed a specialist contractor and received an invoice confirming the work is complete. The doors look good, the decoration is finished and everything appears to be in order.

But can the contractor actually demonstrate that the installation meets the required specification? That's a different question to whether the doors look right, and it's one we see left unasked more often than you'd expect, once a project appears finished.

Why Fire Door Performance Depends on the Whole Assembly, Not Just the Leaf

A fire door's performance depends on the complete assembly, meaning the leaf, frame, glazing, seals, ironmongery and how all of those components work together. Buying a certified product is an important starting point, but performance also depends on correct installation. Small changes to the specified components, made on site for practical reasons, can affect the result without anyone intending to compromise the door's performance.

This is one of the reasons fire door replacement can turn out to be more complicated than expected, particularly in existing buildings where the surrounding construction wasn't designed with the new doorset in mind.

Start with a Proper Survey, Not Just a Measurement

The process should start with a proper survey rather than a quick measurement of the existing door leaf. A thorough survey measures the structural opening, checks the wall construction and condition, confirms the finished floor level and establishes how the frame will be secured.

Measuring only the existing leaf can leave real problems undiscovered until installation is already underway. An oversized opening, a damaged wall edge or an unsuitable fixing position all need an agreed solution, ideally identified and resolved before ordering, with responsibility for any opening repairs clearly included in the scope of works.

Define the Required Performance Before You Order

The required performance should be confirmed before choosing the product. A proper specification identifies the necessary fire resistance, smoke control and any additional requirements such as security, accessibility or exposure to external weather.

A description such as "fire-rated door" doesn't provide enough detail to order the right product or to verify the installation afterwards. Without a clear specification, there's no clear benchmark for either side to check the finished work against.

Installation Details That Actually Matter

Once the product is chosen, the manufacturer's installation instructions for that particular product need to be followed precisely. Frame specification, compatible hardware, seal arrangements and operating gaps all affect whether the door performs as tested.

At completion, the door should operate correctly, and where self-closing is required, it should close fully into its intended position and engage the latch where one is fitted. Gaps should be checked against the applicable product documentation, including the threshold detail, rather than judged by eye.

Understanding Test Reports and Global Assessments

Understanding the supporting evidence behind a fire door is just as important as the physical installation itself.

A test report records the performance of one particular tested construction. A global assessment, sometimes called a product assessment, explains which variations from that tested construction are supported by the underlying test evidence. It is a technical justification for the expected performance of products or variations that haven't themselves been through the exact fire test, not unrestricted permission to change the design however the installer sees fit.

What to Ask When Reviewing the Evidence

When reviewing the evidence for a specific project, it's worth asking the contractor to identify the relevant report number, its revision and the sections covering the arrangement actually installed. The review should cover the door size and configuration, frame, glazing, hardware, seals, supporting wall and installation detail, and should include the limitations and referenced drawings, not just the headline conclusions.

A statement of "60 minutes" on its own doesn't explain whether your particular site arrangement is actually covered by that evidence. Where an installation falls outside the documented scope, ask for a written technical resolution backed by suitable evidence, rather than accepting a general reassurance in its place.

The Frame-to-Wall Gap: The Detail Most Likely to Be Hidden

One area that deserves particular attention is the gap between the frame and the surrounding wall. Once architraves are fitted, this gap becomes completely concealed, so a neatly finished door can easily hide fire stopping work that was never properly checked.

The fire stopping system used here must be suitable for the actual joint involved. In our experience, the things that actually matter at this junction are proven fire performance for this exact configuration, the materials on either side of the gap, the gap width and the thickness of the frame itself. A product simply being described as "fire-rated" doesn't, by itself, establish that it's suitable for this particular frame-to-wall application.

It's worth asking for the exact product name and the installation detail that supports its use. That detail should establish the permitted gap, the required seal depth, the backing material and whether sealing is required on one or both sides. These requirements should match both the doorset documentation and the actual wall construction on site, not just a generic data sheet.

Selecting an intumescent sealant or foam simply because it carries a high fire resistance claim is not enough on its own. The evidence needs to cover how the product will actually be used on this specific project.

If plasterboard strips or other materials are proposed to reduce the size of an opening, it's reasonable to ask how they'll be supported, fixed and incorporated into the wall detail. Filling the visible edge doesn't explain what has happened deeper within the opening, which is why arranging for concealed work to be photographed and checked before architraves go on is so valuable.

Why Independent Inspection During the Works Matters

This is where independent inspection can add real value, and it's a step we'd always encourage. Involving a competent inspector while the work is still progressing, particularly where existing wall conditions or unusual details raise questions, gives you a much better chance of catching problems while they can still be resolved.

An inspection carried out after decoration is complete may be unable to verify concealed fixings or fire stopping without opening the work back up again, which is disruptive and costly compared with checking it at the right moment.

Fixings: The frame must be securely fixed to a sound, stable supporting wall. For stud partitions, the supporting stud must incorporate timber infill where required by the tested installation detail. The fixing type, size, spacing and embedment must follow the doorset manufacturer’s tested details.
Fixings: The frame must be securely fixed to a sound, stable supporting wall. For stud partitions, the supporting stud must incorporate timber infill where required by the tested installation detail. The fixing type, size, spacing and embedment must follow the doorset manufacturer’s tested details.

It's worth agreeing the inspection scope in advance. Will every door be inspected, or only a sample? Will the inspector review the supporting documents as well as the physical installation? Will concealed work actually be witnessed? A good report should state clearly what was checked, what could not be verified and what remains outstanding. A sampled inspection should never be presented as confirmation that every door in the building has been checked.

Third-party contractor certification and an independent project inspection serve different purposes and shouldn't be treated as interchangeable. When appointing a contractor, it's worth verifying the relevant certification and its scope. When commissioning an inspection, ask for findings linked specifically to the project specification and the applicable product evidence, rather than a generic pass or fail.

What a Proper Handover Pack Should Include

Handover deserves just as much planning as the installation itself. For a fuller breakdown of what this should look like in practice, see our guide on what you should receive at handover. At a minimum, a complete handover pack should include a door schedule with unique references, product identification, the applicable certificates and supporting evidence, installation instructions, records of concealed work, completed inspection records and details of any agreed variations. Installation certification should be included where it's provided under the appointed scheme, along with a record of how any defects were identified and resolved.

This information should be kept in a project-specific operation and maintenance manual. The O&M manual should allow the building manager to identify exactly what was installed, understand how it should be maintained, and establish which replacement components are suitable if a part ever needs changing. A folder of unrelated manufacturer brochures provides little practical help when a closer fails or a door needs adjusting years later.

This also ties in with the Golden Thread of information. An O&M manual built around real, project-specific evidence is effectively the Golden Thread for your fire doors in practice, a single accurate record that follows the building rather than a box of paperwork nobody can quite account for a few years on.

In England, where Regulation 38 applies, fire safety information must be provided to support the building's ongoing fire safety management. The handover documents therefore serve a genuinely practical purpose beyond simply completing the contractor's own paperwork.

Questions to Ask If You Have Concerns

If you have concerns about an existing or newly completed installation, it helps to challenge it with clear, evidence-based questions rather than general ones:

  • Please show which installation detail covers this specific arrangement.
  • Can you provide records of the frame fixings and fire stopping from before they were concealed?
  • Which items remain unverified, and how will they be resolved?

It's worth recording each concern against the relevant door reference and agreeing what evidence or corrective work is needed to close it out. Missing documentation doesn't automatically mean a door will fail in a fire, but it does mean its performance remains unverified, which is a different and arguably more frustrating position to be in.

Frequently Asked Questions

If a door is certified, does that guarantee the installation is compliant?

Not on its own. Certification confirms the product has been tested, but the finished installation also depends on correct survey, specification and fitting, all of which need their own evidence.

What's the difference between a test report and a global assessment?

A test report covers one specific tested construction. A global assessment explains which variations from that construction are supported by the underlying evidence, rather than being open permission to change the design freely.

Why does the frame-to-wall gap matter so much?

It's usually hidden behind architraves once the job is finished, so if the fire stopping there wasn't done correctly, there's often no way to tell just by looking at the completed door.

What should I do if I'm not confident about an existing installation?

Ask the contractor or a competent inspector for the specific evidence covering your installation, including report references, installation details and any concealed work records, and treat gaps in that evidence as items to resolve rather than ignore.

Where This Fits with Our Services

Getting a fire door installation right the first time, and being able to prove it afterwards, comes down to the survey, the evidence and the handover documentation as much as the product itself.

Crown Fire Systems provides fire door installation backed by proper surveys, documented evidence and full handover packs, alongside our fire stopping systems and fire safety inspections and surveys for existing installations you're not confident about. Have a look at our full services, or get in touch if you'd like a second opinion on a recent fire door project.